- Spare parts for Unisab III Operating manual Unisab III 005650 en 2013 10 4 48 Page 7 Operating Unisab Iii Control Unisab III can be linked to and communicate with former Sabroe control units such as Unisab II Unisab III is operated by means of a front panel as shown in Fig 3 Unisab 2 Manual orrisrestaurant com - Sabroe unisab 2 manual.
- Manual Unisab Ii Manual Unisab II The electric wiring must be carried out according to the wiring diagrams for UNISAB II at the end of this manual. Note in particular a. That no.Description of UNISAB II control The purpose of the UNISAB II control system is to monitor, protect, control and regulate reciprocating and screw compressors.
- Sabroe UniSAB III systems controllers The UniSAB III systems controllers are core connectivity hubs that help make sure that refrigeration installations have the best possible performance, maximum uptime and lowest possible operating costs.
Unisab III can be linked to and communicate with former Sabroe control units such as Unisab II. Unisab III is operated by means of a front panel as shown in Fig. The front panel is well- arranged with only a few keys and a distinct display. Read and Download Sabroe Unisab 3 Manual Free Ebooks in PDF format - ASID99 PROCEEDINGS OF THE 5TH Page 11/27. Read PDF Unisab 3 Manual ASIAN SYMPOSIUM ON INFORMATION.
Sabroe Unisab Ii Manual
Integrated systems controller for refrigeration compressors, chillers and heat pumps.
Sabroe Unisab 2 Manual
- Functionality
- Connectivity
- Specifications
- Advantages
- Retrofit
- Service on demand schedule
- Unisab app for smartphone
- Configurable for both screw compressors and reciprocating compressors, with or without variable-speed drive (VSD), and using any refrigerant
- Built-in regulation of suction pressure, water temperature, discharge pressure, etc.
- Limitations on suction pressure, discharge pressure, motor current, etc.
- Logging of operating history and profiles for effective fault-finding and diagnosis
- Email dispatch in case of alarm or shut down.
The Unisab III systems controller has normal industry-standard communication ports fitted as standard, and therefore does not require additional communication gateways.
Connectivity | Multiple communication ports, including Modbus TCP, Profibus DP and Sequence Bus, as standard |
Smartphone app | Available for both iOS and Android devices |
Sequencing | As many as 14 refrigeration compressors, chillers and heat pumps of different makes and types can be linked in sequence, to ensure effective load sharing and capacity optimisation |
Diagnostics | Detailed operating data documenting 30 shut-down situations |
Refrigerants | Pre-loaded with the requisite data about all refrigerants normally used |
Operating languages | Multiple languages available as standard, with additional languages as options |
Enclosure | IP54 |
Ambient temperature | 0–55 °C |
Power supply | 85–250 volt AC, 50–60 Hz |
Dimensions (H x W x D) | 380 x 300 x 210 mm |
Weight | 6,5 kg |
Advantages | Benefits |
Single, fully integrated control system for use with virtually all types of compressors and chillers | Ensures more effective monitoring, control and diagnostics of a wide range of key refrigeration installations |
Easy to integrate into the vast majority of industrial control systems, providing seamless transfer of data between systems | Ensures effective management of important operating data and secures the production process for best performance |
Monitoring, control and diagnostics capabilities combined in one compact, integrated unit | Does away with the need for multiple systems, resulting in significant equipment savings |
Compressor sequencing and load sharing are possible without additional equipment | Keeps power consumption to a minimum and reduces operating costs |
Intuitive, easy-to-use interface, with a consistent “look and feel” | Requires fewer operator skills, resulting in lower training costs |
A wide range of Unisab III retrofit kits are available to provide all the advantages of upgrading a wide range of existing compressors to a modern controls standard for improved performance and control system integration.